Golden Sine Wave UPS systems are technologically superior and can be called true intelligent UPS because of its advanced features which will give more than expected. As a quality conscious company, each and every component used in our products are approved by reputed organizations like C-DOT, DOT etc. Advanced Multi-step charger (Charges deep discharged batteries) makes our UPS systems different from others because of its unique charging method which extends the battery life with very low maintenance. Sine wave system gives you non-stop protection for all your valuable appliances with its super silent operation. Golden Sine wave UPS systems come with an intelligent monitoring LCD display which makes it truly user-friendly, which in turn avoids unnecessary visit of service person.

  • DSP Sinewave UPS
  • Full Featured LCD Display
  • Wide Input Mains Operating Range
  • Intelligent 5 Step Charging
  • Micro Controlled Based Battery Management
  • Charges Even Deep Discharged Batteries
  • Fast Switchover Avoids Rebooting of PC's
  • Automotive / Tubular Battery Selector Switch
  • Aesthetic & Elegant Look
  • Temperature Controlled Fan Operation
  • Audio Alarms for Low Battery & Overload
  • No Humming Noise
  • Auto Reset for Overload

MODEL 850 VA - 1000 VA 1000 VA - 2000 VA 2000 VA - 5000 VA
Voltage Range INV Mode 130V AC - 280V AC / UPS Mode 170V AC - 265V AC
Frequency 50 Hz ± 5%
OUPUT
Mains Mode Same as EB
On INV Mode 230V AC ± 2%
Frequency 50 Hz ± 1%
Transfer Time INV Mode 12 - 15 ms / UPS Mode 4 - 8 ms
Load Power Factor 0.8 Lagging
Overload 100% Continuous / 130% for 10 Sec / 150% for 1 Sec
Efficiency 90%
BATTERY
Battery Voltage 12V DC 24V DC 36V / 48V / 72V DC
Backup Depending on requirement
Charger Type Multistep Charger (Charges deep discharged battery)
Charging Time 7 - 8 hr
Protection Short Circuit, Output Reverse, Deep Discharge & Over Charge
Indications LCD Display
Mains Voltage, Inverter Output Voltage,
Charging Mode & Current, Battery Voltage,
Load in Watts, UPS Ready/Not Ready, Battery Low,
Overload, Short Circuit, Solar Charging
Alarm Low Battery / Over Load / UPS Mode / Over Temperature
ENVIRONMENT
Operating Temperature 0° - 60° C
Relative Humidity 0 - 95% Non-condensive
Acoustic Noise < 60 db